ASSUMPTIONS FOR SUITABLE COMBINATIONS:

  • Heat transfer should be enough to get 53 C hot water at 10 C Brine with one load up (65 C VBmax).
  • Pressure drop over the coil/coils should not be bigger than the VB-pump capacity.
  • Less power than 5 kW / 500l hot water volume, gives to long reloading times > 5 h

GROUND SOURCE - SUITABLE COMBINATIONS WITH VPB

ModelVPB 200 / VPB S200VPB 300 / VPB S300VPB 500VPB 750-2VPB 1000 p
6okokok--
8okokokok-
10okokokokok
12okokokokok
15min 2 ea.min 2 ea.okokok
16okokokokok
17min 2 ea.min 2 ea.okokok
24*okokokokok
24min 2 ea.min 2 ea.min 2 ea.min 2 ea.ok
25min 2 ea.min 2 ea.okokok
30*min 2 ea.min 2 ea.okokok
30--min 2 ea.min 2 ea.ok
40*min 2 ea.min 2 ea.min 2 ea.okok
40---min 2 ea.min 2 ea.
43*min 2 ea.min 2 ea.okokok
43---min 2 ea.min 2 ea.
60*--min 2 ea.min 2 ea.ok
60----min 2 ea.

* Only one compressor

p = parallel connected coils

s = serial connected coils

Using more than one tank (VPB): Always connect CW and HW parallel and load the tanks parallel with flow adjusting valves.

GROUND SOURCE - SUITABLE COMBINATIONS WITH AHPS AND VPA

ModelAHPSVPA 200/70VPA 300/200VPA 450/300VPAS 300/450
6okok---
8okokokokok
10okokokokok
12okokokokok
15okmin 2 ea.okokok
16okokokokok
17okmin 2 ea.okokok
24*okokokokok
24okmin 2 ea.min 2 ea.okmin 2 ea.
25okmin 2 ea.okokok
30*okmin 2 ea.okokok
30min 2 ea.-min 2 ea.min 2 ea.min 2 ea.
40*okmin 2 ea.min 2 ea.okmin 2 ea.
40min 2 ea.--min 2 ea.-
43*okmin 2 ea.okokok
43min 2 ea.--min 2 ea.-
60*min 2 ea.-min 2 ea.min 2 ea.min 2 ea.
60min 3 ea.--min 3 ea.-

* Only one compressor

Using more than one tank (VPA): Always connect CW and HW in serial, and load the tanks in serial, counter flow.

AIR/WATER - SUITABLE COMBINATIONS WITH VPB

ModelVPB 200 / VPB S200*VPB 300 / VPB S300*VPBS 300*VPB 500**VPB 750-2**VPB 1000**
F2120-8okokokokokok
F2120-12okokokokokok
F2120-16okokokokokok
F2120-20---okokok
F2040-8okokokokokok
F2040-12okokokokokok
F2040-16---okokok

* Only for use with air / water heat pump where the additive is placed before the shuttle valve.

** Addition of the tank is required when installing air/water heat pump when the property heating is a priority when operating under the balance temperature.

AIR/WATER - SUITABLE COMBINATIONS WITH AHPS AND VPA

ModelAHPS 300*VPA 300/200**VPA 450/300**VPA 300/450**
F2120-8okokokok
F2120-12okokokok
F2120-16okokokok
F2120-20okokokok
F2040-8okokokok
F2040-12okokokok
F2040-16okokokok

* Only for use with air / water heat pump where the additive is placed before the shuttle valve.

** Addition of the tank is required when installing air/water heat pump when the property heating is a priority when operating under the balance temperature.