-QM42 -QM12 -CM2 -FL3 -QM31 -QZ2 -FL2 -CM1 -EB100 - B T1 -BP5 -QZ3 -EB100 P -QM34 XL 1 6 9 7 2 XL 1 6 9 7 2 -CP1 -EB100 - B T6 -EB100 - B T7 -CP4 -QZ 1 -F Q 3 -QZ1-GP11 -QZ 1 -RM 1 -QZ1-RN1 -QZ1 -QZ 1 -F Q 3 -QZ1-GP11 -QZ 1 -RM 1 -QZ1-RN1 -QZ1 -EB100-GP10 -CM3 -BP6 -FL3 -EP44 - AA25 -EP44-QN18 -EP 44 - B T6 4 -EP44-GP10 -EP 44 - B T6 5 -EP 44 - R M 1 -EP44 P -CM3 -BP6 -FL3 P -EQ1- B T57 -EQ1-QN18 -EQ1-QN12 -EQ1 - AA25 -EQ1 -CP10.2 -EP45 -EQ 1 - B T6 4 -EP 12 -GP 3 -EP12-HQ40 -EP12-EP4 -EP12 - AA25 -EP12 -CP3 -CP10.1 -EB100- B T25 -EP21-GP10 -EP21- B T2 -EP 21 - AA2 5 -EP21- B T3 -EP21-QN25 -EP21 -CL11-HQ4 -CL11- B T51 -C L11 -GP 9 -CL11-EP5 -CL11-QN19 -CL11 - AA25 -CL11 - AZ10 -RM1 -CM3 -BP6 -FL3 P - AZ10 - AZ30 -GC1 - AZ11 -CM3 -BP6 -FL3 P -EM1 - AA25 -EM1- B T52 -EM1-QN11 -EM 1 -EM1 -EB1 - AA25 -EB1 -RM1 -QZ20 -EB100 -GP7 -RM2 -EQ1-RM1 -EQ1-GP14 -EQ1-EP6 -EQ1-QN36 -EQ1-GP10 -EQ1 -EQ1-RM2 -EQ1- B T75 -EQ1-RM1 -EQ1-EP6 -EQ1-QN36 -EQ1-GP10 -EQ1 -EQ1-GP14 -EQ1-CM3 -EQ1-BP6 -EQ1-FL3 P -EQ1-RM2 -EP1 -C T 1 -EP1-CT2 -EP1-CT3 -EP1-EP7 -EP 1 - Q N 1 1 -EP1 -EP1- B T52 -EQ1-QN12 -EB100 - B T25 -EB100- B T71 -CP1-FL6 -CP1 - WM3.2 -CP1 - WM3.1 -CP1-CM4 -CP1 -QN17 -CP1 -RM1 -CP1 -QM30 -CP1-FL1 -CP1-FL5

Protective and safety equipment as well as components that facilitate servicing (e.g. non-return valves, safety valves, overflow valves, shut-off valves) must be installed in accordance with national regulations and standards.

Important component information

Pay attention to supplementary information for the following components:

Function

Heat pump

The compressor in a F1145 is an on/off type. The compressor’s full power is routed to heating, hot water, cooling or pool heating. If the power is not sufficient for the heating demand, additional heating is connected automatically.

The compressor in a F1155 is inverter-controlled. The compressor’s power is adjusted according to the demand and routed to heating, hot water, cooling or pool heating. If the power is not sufficient for the heating demand, additional heating is connected automatically.

Operating modes

Heat production

NIBE F1145/F1155 is supplied with a heating control system, which means that the heating supply to the house takes place according to selected settings. When connecting to a system with thermostats on all radiators (or underfloor heating coils), either a bypass valve must be fitted or some of the thermostats must be removed to ensure there is sufficient flow. For more information about heat production, see the Installer Manual.

Hot water production

If hot water heating is required, one or more external water heaters/accumulator tanks are docked.

When there is demand for hot water, NIBE F1145/F1155 prioritises this and switches to hot water mode. There is no heat production in this mode.

If the hot water temperature exceeds 60 °C, the installation must be supplemented with a mixing valve.

For more information about hot water production, see the manual for NIBE F1145/F1155 and/or the water heater’s/accumulator tank’s manual.

Cooling production

Passive cooling, cooling function without the compressor running, is achieved by connecting a cooling system to the heat pump’s brine circuit. The collector’s low temperature can be utilised for comfort cooling.

When cooling is required (activated from the outdoor temperature sensor and any room sensor) the circulation pump is activated and the shunt valve provides the correct supply temperature.

Functions/accessories

External heating medium pump

With the AXC 40 accessory (one for each accessory function that is to be used), an external heating medium pump can be connected to NIBE F1145/F1155, if the alarm relay (the AUX output) is activated for another function. If the AUX output cannot be used for an external heating medium pump, the function is available in:

  • addition

  • shunt-controlled additional heat

  • pool

Heating system 2

This function requires the ECS 40/41 accessory. Shunt valve, supply and return line sensors as well as circulation pump are connected to other heating circuits with a lower temperature demand (e.g. underfloor heating system). The temperature in the extra heating system follows the selected curve slope and offset setting. Up to 8 extra heating systems can be connected to the installation. For further information, see the Installer Manual for the accessory. See the valve’s manual for the port description.

Extra hot water heaters

The system should be supplemented with an extra water heater, if a large bath tub or other significant consumer of hot water is installed.

External brine pump

If there is a large pressure drop over the brine side, an external brine pump may be required.

HRV unit

This function requires the accessory ERS, which is controlled by NIBE F1145/F1155. ERS recovers the energy from the ventilation air and supplies it to the property.

For further information, see the Installer Manual for the accessory.

Exhaust air recovery

This function requires the accessory NIBE FLM. NIBE FLM is an exhaust air module that is controlled by NIBE F1145/F1155. NIBE FLM recovers energy from the exhaust air and supplies it to the brine.

For further information, see the Installer Manual for the accessory.

Ground water system

This connection enables the use of ground water as heat source. The ground water is pumped up to an intermediate heat exchanger. An intermediate heat exchanger is used to protect the heat pump's exchanger from dirt and freezing. The water is released into a buried filtration unit or a drilled well.

The ground water pump runs at the same time as the brine pump.

Active/passive cooling (cooling in 4-pipe system)

With the accessory ACS 45, a separate cooling system can be connected via a reversing valve. ACS 45 allows both heat and cooling production independently of each other.

Passive cooling occurs without the compressor running, active cooling occurs when the compressor is running. The cooling system is connected to the heat pump’s brine circuit.

When cooling is required (activated from the outdoor temperature sensor EB100-BT1 and room sensor EB100-BT50, where applicable), the shunt valve EQ1-QN18 and the circulation pump EQ1-GP10 are activated.

See the valve’s manual for a port description.

Heat dump

If there is excess heat, this is dumped to a coolant radiator or to the collector.

Passive cooling (cooling in 4-pipe system)

This function requires the AXC 40 accessory. The cooling system is connected to the heat pump brine circuit, through which cooling is supplied from the collector via the circulation pump and the shunt valve.

When cooling is required (activated from the outdoor temperature sensor EB100-BT1 and room sensor EB100-BT50, where applicable), EP44-QN18 and the circulation pump EP44-GP10 are activated.

The shunt valve regulates so that the cooling sensor reaches the current set point value corresponding to the outdoor temperature and the set min. value for the cooling temperature (to prevent condensation).

If the NIBE FLM accessory is installed with AXC 40, the cooling output will be reduced.

See the valve’s manual for a port description.

Pool

With the POOL 40 accessory, the heat pump can be used to heat a pool.

For further information, see the Installer Manual for the accessory.

Filling kit

In order to fill the system easily with brine, the accessories KB 25/KB 32 are available. These consist of a filterball, reversing valve and shut-off/filling valves, and are available in two sizes.

KB 25 for heat pump sizes up to 12 kW and KB 32 for heat pump sizes up to 30 kW.

Solar panels

This function requires the NIBE PV accessory. NIBE PV is a complete modular system with solar panels in several basic outputs. NIBE PV is connected to NIBE F1145/F1155, which adjusts to the generated solar electricity produced.

For further information, see the Installer Manual for the accessory.

Addition

Additional heat that requires the AXC 40 accessory. AXC 40 via a control signal, can control step-controlled additional heat. The additional heat is used for heat production.

For further information, see the Installer Manual for the accessory.

Shunt controlled additional heat

Additional heat that requires the AXC 40 accessory. AXC 40 via a control signal, can control additional heat, which can also be prioritised. The additional heat is used for heat production.

For further information, see the Installer Manual for the accessory.

Buffer vessel (UKV)

A 3-pipe-connected buffer vessel is used when the system volume in the climate system is below the minimum recommended volume for the heat pump and/or the flow in the heating system is restricted without control.

For further information, see the Installer Manual for the accessory.

Hot water circulation

A circulation pump can be controlled by NIBE F1145/F1155 to circulate the hot water. The circulating water must have a temperature that prevents bacterial growth and scalding, and national standards must be satisfied. See the appropriate Installer Manual for more information.

List of components

Designation

Name

Specification

Part No.

Comments

-AA35-BT1

Outside sensor

Included in NIBE F1145/F1155

Modbus: 40004

-AA35-BT6

Controlling hot water sensor

Included in NIBE F1145/F1155

Modbus: 40014

-AA35-BT7

Display hot water sensor

Included in NIBE F1145/F1155

Modbus: 40013

-AA35-BT25

External supply temperature sensor

Included in NIBE F1145/F1155

Modbus: 40071

-AA35-BT63

External supply temperature sensor before QN10

Included in NIBE F1145/F1155

Modbus: 40121

-AA35-BT71

External return line sensor

Included in NIBE F1145/F1155

Modbus: 40152

-AA35-GP10

External heating medium pump

Modbus: 43189

-AA35-GP12

Charge pump for EB101

NIBE CPD 11

Modbus: 44396

067 321 / 067 320

-AA35-GP12.1

Charge pump for EB101

NIBE CPD 11

Modbus: 44396

067 321 / 067 320

-AA35-GP12.2

Charge pump for EB102

NIBE CPD 11

Modbus: 44395

067 321 / 067 320

-AA35-GP12.3

Charge pump for EB103

NIBE CPD 11

Modbus: 44394

067 321 / 067 320

-AA35-GP12.4

Charge pump for EB104

NIBE CPD 11

Modbus: 44393

067 321 / 067 320

-AA35-GP12.5

Charge pump for EB105

NIBE CPD 11

Modbus: 44393

067 321 / 067 320

-AA35-QN10

Reversing valve, heating/hot water

See the valve’s manual for a port description.

-AA35-QN43

Bypass valve, cooling operation

-EB100

Heat pump system (master unit)

NIBE F1145/F1155

-EB100F1355

Heat pump system (master unit)

F1155

-EB100F1330

Heat pump system (master unit)

F1145

-EB100F1360

Heat pump system (master unit)

?

-EP14

Cooling module

See the Installer Manual for more information about the relevant cooling module.

-EP15

Cooling module

See the Installer Manual for more information about the relevant cooling module.

-EB100-BT1

Outside sensor

Included in NIBE F1145/F1155

Modbus: 40004

-BT1

Outside sensor

Included in NIBE F1145/F1155

Modbus: 40004

-BT6

Controlling hot water sensor

Included in NIBE F1145/F1155

Modbus: 40014

-EB100-BT6

Controlling hot water sensor

Included in NIBE F1145/F1155

Modbus: 40014

-EB100-BT7

Display hot water sensor

Included in NIBE F1145/F1155

Modbus: 40013

-BT7

Display hot water sensor

Included in NIBE F1145/F1155

Modbus: 40013

-EB100-BT25

External supply temperature sensor

Included in NIBE F1145/F1155

Modbus: 40071

-BT25

External supply temperature sensor

-EB100-BT71

External return line sensor

Modbus: 40152

-BT71

External return line sensor

Modbus: 40152

-EB100-CM4

Expansion vessel, hot water

Included in NIBE F1145/F1155

-EB100-FL1

Safety valve, hot water

Included in NIBE F1145/F1155

-EB100-FL5

T&P valve

Included in NIBE F1145/F1155

-EB100-FL6

Vacuum valve

Included in NIBE F1145/F1155

-EB100-FQ1

Mixing valve

Included in NIBE F1145/F1155

-EB100-QN17

Pressure reduction valve

Included in NIBE F1145/F1155

-EB100-QM30

Shut-off valve

-EB100-RM1

Non-return valve

-EB100-WM3.1

Tundish, cold water

Included in NIBE F1145/F1155

-EB100-WM3.2

Tundish, T&P valve

Included in NIBE F1145/F1155

-EB100-GP7

External brine pump

-EB100-GP10

External heating medium pump

Modbus: 43189

-GP10

External heating medium pump

Modbus: 43189

-EB100-QN10

Reversing valve, heating/hot water

See the valve’s manual for a port description.

-QN10

Reversing valve, heating/hot water

See the valve’s manual for a port description.

-EP4

Heat exchanger, groundwater

-FL3

Safety valve, brine

Included in NIBE F1145/F1155

-FL3

Safety valve, brine

Included in NIBE F1145/F1155

-FL311xx

Safety valve, brine

Included in F1155/F1145/NIBE F1145/F1155

-FL10

Safety valve, brine

-FL10-0

Safety valve, brine

-FL11-0

Safety valve, brine

-FL12-0

Safety valve, heating medium

-FL13-0

Safety valve, heating medium

-HQ1-F1360

Particle filter, brine

Included in ?

-HQ1-F1330

Particle filter, brine

Included in F1145

-HQ2-F1360

Particle filter, brine

Included in ?

-HQ2-F1330

Particle filter, brine

Included in F1145

-HQ3-F1360

Particle filter, heating medium

Included in ?

-HQ3-F1330

Particle filter, heating medium

Included in F1145

-HQ4-F1360

Particle filter, heating medium

Included in ?

-HQ4-F1330

Particle filter, heating medium

Included in F1145

-GP16-0

Circulation pump, brine

Included in F1145 40/60

Modbus: 43439 (input)

-QN11

Shuttle valve

-QM12

Filling valve, brine

-QM21

Vent valve, brine

-QM31

Shut-off valve, heating medium supply line

-QM32

Shut-off valve, heating medium return line

-QM33

Shut-off valve, brine in

-QM34

Shut off valve, brine out

-QM40

Shut-off valve

-QM42

Shut-off valve, brine in

-QM50-0

Shut off valve, brine

-QM51-0

Shut off valve, brine

-QM52-0

Shut off valve, brine

-QM53-0

Shut off valve, brine

-QM54-0

Shut-off valve, heating medium

-QM55-0

Shut-off valve, heating medium

-QM56-0

Shut-off valve, heating medium

-QM57-0

Shut-off valve, heating medium

-QZ2

Filterball, heating medium

Included in F1155

The F1145 includes a particle filter, which should be supplemented with a shut-off valve.

-QZ2.1-0

Filterball, heating medium

Included in F1155

-QZ2.2-0

Filterball, heating medium

Included in F1155

-QZ2.3-0

Filterball, heating medium

Included in F1155

-QZ2.4-0

Filterball, heating medium

Included in F1155

-QZ3

Filterball, brine

Included in F1155

The F1145 includes a particle filter, which should be supplemented with a shut-off valve.

-QZ4

Filterball, heating medium

Included in F1155

The F1145 includes a particle filter, which should be supplemented with a shut-off valve.

-QZ5

Filterball, heating medium

Included in F1155

The F1145 includes a particle filter, which should be supplemented with a shut-off valve.

-RM10-F1360

Non-return valve

-RM10-F1330

Non-return valve

Included in F1145

-RM10-F1355

Non-return valve

Included in F1155

-RM11-F1360

Non-return valve

Included in ?

-RM11-F1330

Non-return valve

Included in F1145

-RM11-F1355

Non-return valve

Included in F1155

-RM12-F1360

Non-return valve

Included in ?

-RM12-F1330

Non-return valve

Included in F1145

-RM12-F1355

Non-return valve

Included in F1155

-RM13-F1360

Non-return valve

Included in ?

-RM13-F1330

Non-return valve

Included in F1145

-RM13-F1355

Non-return valve

Included in F1155

-RN20

Trim valve

-RN21

Trim valve

-EB10011xx

Heat pump system (master unit)

F1155

-EB10012xx

Heat pump system (master unit)

F1145

-EB10013xx

Heat pump system (master unit)

?

-BT111xx

Outside sensor

Included in F1155

Modbus: 40004

-BT112xx

Outside sensor

Included in F1145

Modbus: 40004

-BT113xx

Outside sensor

Included in ?

Modbus: 40004

-QZ311xx

Filterball, brine

Included in F1155

-QZ312xx

Filterball, brine

Included in F1145

-EB100-BT2511xx

External supply temperature sensor

Included in F1155/NIBE F1145/F1155

Modbus: 40071

-EB100-BT7111xx

External return line sensor

Included in F1155/NIBE F1145/F1155

Modbus: 40152

-EB100-QZ211xx

Filterball, heating medium

Included in F1155

-EB100-QZ212xx

Filterball, heating medium

Included in F1145

-EB101F1355

Heat pump system 1

F1155

-EB101F1330

Heat pump system 1

F1145

-EB101F1360

Heat pump system 1

?

-EB101

Heat pump system 1

-GP16-1

Circulation pump, brine

Included in F1145 40/60

Modbus: 43439 (input)

-EB101-FL10

Safety valve, brine

-FL10-1

Safety valve, brine

-FL11-1

Safety valve, brine

-FL12-1

Safety valve, heating medium

-FL13-1

Safety valve, heating medium

-HQ1-1361

Particle filter, brine

Included in ?

-HQ1-F1330-1

Particle filter, brine

Included in F1145

-HQ2-1362

Particle filter, brine

Included in ?

-HQ2-F1330-1

Particle filter, brine

Included in F1145

-HQ3-1362

Particle filter, heating medium

Included in ?

-HQ3-F1330-1

Particle filter, heating medium

Included in F1145

-HQ4-1362

Particle filter, heating medium

Included in ?

-HQ4-F1330-1

Particle filter, heating medium

Included in F1145

-EB101-QM1

Drain valve, heating medium

-EB101-QM40

Shut-off valve, heating medium

-QM50-1

Shut off valve, brine

-QM51-1

Shut off valve, brine

-QM52-1

Shut off valve, brine

-QM53-1

Shut off valve, brine

-QM54-1

Shut-off valve, heating medium

-QM55-1

Shut-off valve, heating medium

-QM56-1

Shut-off valve, heating medium

-QM57-1

Shut-off valve, heating medium

-QZ2.1-1

Filterball, brine

Included in F1155

-QZ2.2-1

Filterball, brine

Included in F1155

-QZ2.3-1

Filterball, heating medium

Included in F1155

-QZ2.4-1

Filterball, heating medium

Included in F1155

-RM10-F1361

Non-return valve

-RM10-F1330-1

Non-return valve

Included in F1145

-RM10-F1355-1

Non-return valve

Included in F1155

-RM11-F1361

Non-return valve

Included in ?

-RM11-F1330-1

Non-return valve

Included in F1145

-RM11-F1355-1

Non-return valve

Included in F1155

-RM12-F1361

Non-return valve

Included in ?

-RM12-F1330-1

Non-return valve

Included in F1145

-RM12-F1355-1

Non-return valve

Included in F1155

-RM13-F1361

Non-return valve

Included in ?

-RM13-F1330-1

Non-return valve

Included in F1145

-RM13-F1355-1

Non-return valve

Included in F1155

-EB102

Heat pump system 2

-EB102F1355

Heat pump system 2

F1155

-EB102F1330

Heat pump system 2

F1145

-EB102F1360

Heat pump system 2

?

-GP16-2

Circulation pump, brine

Included in F1145 40/60

Modbus: 43439 (input)

-FL10-2

Safety valve, brine

-FL11-2

Safety valve, brine

-FL12-2

Safety valve, heating medium

-FL13-2

Safety valve, heating medium

-HQ1-F1362

Particle filter, brine

Included in ?

-HQ1-F1330-2

Particle filter, brine

Included in F1145

-HQ2-F1362

Particle filter, brine

Included in ?

-HQ2-F1330-2

Particle filter, brine

Included in F1145

-HQ3-F1362

Particle filter, heating medium

Included in ?

-HQ3-F1330-2

Particle filter, heating medium

Included in F1145

-HQ4-F1362

Particle filter, heating medium

Included in ?

-HQ4-F1330-2

Particle filter, heating medium

Included in F1145

-EB102-QM1

Drain valve, heating medium

-EB102-QM40

Shut-off valve, heating medium

-QM50-2

Shut off valve, brine

-QM51-2

Shut off valve, brine

-QM52-2

Shut off valve, brine

-QM53-2

Shut off valve, brine

-QM54-2

Shut-off valve, heating medium

-QM55-2

Shut-off valve, heating medium

-QM56-2

Shut-off valve, heating medium

-QM57-2

Shut-off valve, heating medium

-QZ2.1-2

Filterball, brine

Included in F1155

-QZ2.2-2

Filterball, brine

Included in F1155

-QZ2.3-2

Filterball, heating medium

Included in F1155

-QZ2.4-2

Filterball, heating medium

Included in F1155

-RM10-F1362

Non-return valve

-RM10-F1330-2

Non-return valve

Included in F1145

-RM10-F1355-2

Non-return valve

Included in F1155

-RM11-F1362

Non-return valve

Included in ?

-RM11-F1330-2

Non-return valve

Included in F1145

-RM11-F1355-2

Non-return valve

Included in F1155

-RM12-F1362

Non-return valve

Included in ?

-RM12-F1330-2

Non-return valve

Included in F1145

-RM12-F1355-2

Non-return valve

Included in F1155

-RM13-F1362

Non-return valve

Included in ?

-RM13-F1330-2

Non-return valve

Included in F1145

-RM13-F1355-2

Non-return valve

Included in F1155

-EB103

Heat pump system 3

-EB103-AA25

AXC module

Included in AXC 40

067 304

-EB103-QM1

Drain valve, heating medium

-EB103-QM40

Shut-off valve, heating medium

-EB104

Heat pump system 4

-EB104-QM1

Drain valve, heating medium

-EB104-QM40

Shut-off valve, heating medium

-EB105-AA25

AXC module

Included in AXC 40

067 304

-EB105-QM1

Drain valve, heating medium

-EB105-QM40

Shut-off valve, heating medium

XL1

Heating medium connection, supply

XL2

Heating medium connection, return

0.1

Ventilation unit 1

-RN1

Trim valve

-AZ10

Exhaust air module

NIBE FLM

067 627

-AZ11

Ventilation module

-AZ10-RM1

Non-return valve

Included in NIBE FLM

-AZ10-RN11

Control valve

Included in NIBE FLM

-AZ10-RN1

Trim valve

Included in NIBE FLM

0

Exhaust air module

NIBE F135

067 075

0

Exhaust air module

NIBE S135

067 075

-AZ30

Ventilation unit

NIBE ERS

-CL11

Pool system

POOL 40

067 062

067 193

-CL11-AA25

AXC module, pool

Included in POOL 40

-CL11-BT25

External supply temperature sensor

Included in POOL 40

Modbus: 40071

-CL11-BT51

Pool sensor

Included in POOL 40

Modbus: 40042

-CL11-EP5

Exchanger, pool

-CL11-GP9

Circulation pump, pool

Modbus: 44749

-CL11-GP12

Charge pump, pool

Included in POOL 40

Modbus: 44749

-CL11-HQ4

Particle filter, pool

-CL11-QN19

Three way valve, pool

Included in POOL 40

Modbus: 43564

See the valve’s manual for a port description.

Max. 17 kW

-CL11-RM1

Non-return valve, pool

-CL12

Pool system 2

POOL 40

067 062

067 193

-CL12-AA25

AXC module, pool

Included in POOL 40

-CL12-BT25

External supply temperature sensor

Included in POOL 40

Modbus: 40071

-CL12-BT51

Pool sensor

Included in POOL 40

Modbus: 40042

-CL12-EP5

Exchanger, pool

-CL12-GP9

Circulation pump, pool

Modbus: 44748

-CL12-GP12

Charge pump, pool

Included in POOL 310

Modbus: 44749

-CL12-HQ4

Particle filter, pool

-CL12-QN19

Three way valve, pool

Included in POOL 40

Modbus: 43564

See the valve’s manual for a port description.

-CL12-RM1

Non-return valve

Included in POOL 40

-CP1

Storage tank

-CP1.1

Storage tank

-CP1.1-CM4

Expansion vessel, hot water

Included in accumulator tank

-CP1-CM4

Expansion vessel, hot water

Included in accumulator tank

-CP1.1-FL1

Safety valve, hot water

-CP1-FL1

Safety valve, hot water

-CP1.1-FL5

T&P valve

Included in accumulator tank

-CP1.2-FL5

T&P valve

Included in accumulator tank

-CP1-FL5

T&P valve

Included in accumulator tank

-CP1.1-FL6

Vacuum valve

Included in accumulator tank

-CP1.2-FL6

Vacuum valve

Included in accumulator tank

-CP1-FL6

Vacuum valve

Included in accumulator tank

-CP1.1-FQ1

Thermal mixing valve

-CP1-FQ1

Thermal mixing valve

-CP1.1-QN17

Pressure reduction valve

Included in accumulator tank

-CP1-QN17

Pressure reduction valve

Included in accumulator tank

-CP1.1-QM30

Shut-off valve

-CP1-QM30

Shut-off valve

-CP1.1-QM40

Shut off valve

Included in accumulator tank

-CP1.2-QM40

Shut off valve

Included in accumulator tank

-CP1.1-RM1

Non-return valve

-CP1-RM1

Non-return valve

-CP1.1-WM3.1

Tundish, cold water

Included in accumulator tank

-CP1-WM3.1

Tundish, cold water

Included in accumulator tank

-CP1.1-WM3.2

Tundish, T&P valve

Included in accumulator tank

-CP1.2-WM3.2

Tundish, T&P valve

Included in accumulator tank

-CP1-WM3.2

Tundish, T&P valve

Included in accumulator tank

-CP1.1-RN1.1

Trim valve

-CP1-RN1.1

Trim valve

-CP1-RN1

Trim valve

-CP1.1-RN1.2

Trim valve

-CP1-RN1.2

Trim valve

-CP1.2

Storage tank

-CP1.2-RN1.1

Trim valve

-CP1.2-RN1.2

Trim valve

-RN60

Trim valve

-RN61

Trim valve

-CP2

Water heater

-CP2-FQ1

Thermal mixing valve

Part no. 624 922

-CP4

Additional water heater

-CP10.4

Tanks

-CP10.4

Storage tank

UKV 20-750 / UKV 20-1000

Size varies depending on the dimensioning of hot water

-CP10.5

Storage tank

UKV 20-750 / UKV 20-1000

Size varies depending on the dimensioning of hot water

-CP10.6

Storage tank

UKV 20-750 / UKV 20-1000

Size varies depending on the dimensioning of hot water

-CP10.7

Storage tank

UKV 20-750 / UKV 20-1000

Size varies depending on the dimensioning of hot water

-EB1

Step-controlled additional heat/electric boiler

Modbus: 43091

-EB1-AA25

AXC module

Included in AXC 40

067 060

-EB1-BT25

Supply temperature sensor, heating medium, external

Included in AXC 40

Modbus: 40071

-EB1-BT52

Boiler sensor

Included in AXC 40

Modbus: 40070

-EB1-CM5

Closed expansion vessel, heating medium

-EB1-EP7

District heating exchanger

-EB1-FL2

Safety valve, heating medium

-EB1-GP10

Circulation pump, heating medium external

Modbus: 43189

-EB1-QM40

Shut-off valve

-EB1-QM41

Shut-off valve

-EB1-QN11

Shuttle valve

See the valve’s manual for a port description.

-EB1-RM5

Non-return valve

-RN1

Trim valve

-EB2

External electrical backup

-EB3

Immersion heater in tank

with junction box K11

IU 3 kW: 218 009

IU 6 kW: 218 011

IU 9 kW: 218 003

018 893

-EB3-QA1

Auxiliary relay

HR 10

067 309

-EB15

Indoor module

NIBE F1145/F1155

-EB15-BT1

Outside sensor

Included in NIBE F1145/F1155

Modbus: 40004

-EB15-BT25

External supply temperature sensor

Included in AXC 40

Modbus: 40071

-EB15-BT25_extcp

External supply temperature sensor

Modbus: 40071

-EB15-CM4

Expansion vessel, hot water

-EB15-GP10

Circulation pump, heating medium external

Modbus: 43189

-EB15-FL1

Safety valve, hot water

-EB15-RM2

Non-return valve

-EB15-QM30

Shut-off valve, hot water

-EB15-WM4

Tundish, T&P valve

Included in NIBE F1145/F1155

XL

XL connections

1

Heating medium connection, supply

2

Heating medium connection, return

3

Cold water connection

4

Hot water connection

5

Hot water circulation connection

6

Brine connection, supply

7

Brine connection, return

8

Docking connection, supply (from heat pump)

9

Docking connection, return (to heat pump)

13

Solar heat connection, supply

14

Solar heat connection, return

18

Docking connection, supply (high temp)

19

Docking connection, return (high temp)

29

T&Pvalve

30

Expansion vessel connection

36

Heating medium connection, supply

37

Heating medium connection, return

39

Docking connection, pool

-EM1

Shunt controlled additional heat

-EM1-AA25

AXC module

Included in AXC 40

067 060

-EM1-QN11

Shunt valve for additional heat

Modbus: 43098

-EM1-BT52

Boiler sensor

Included in AXC 40

Modbus: 40070

-EM1-BT25

Supply temperature sensor, heating medium, external

Included in AXC 40

Modbus: 40071

-EM1-GP10

External heating medium pump

Modbus: 43189

-EM1/EB1

Electric boiler, wood boiler, pellet boiler, oil boiler or district heating

-EM1/EB1-GP10

Circulation pump

Modbus: 43189

-EP1

District heating

-EP1-AA25

AXC module

Included in AXC 40

067 060

-EP1-BT25

External supply temperature sensor

Included in AXC 40

Modbus: 40071

-EP1-BT52

Boiler sensor

Included in AXC 40

Modbus: 40070

-EP1-CM5

Closed expansion vessel, heating medium

-EP1-EP3

District heating exchanger, hot water

-EP1-EP7

District heating exchanger

-EP1-FL2

Safety valve, heating medium

-EP1-GP10

Circulation pump, heating medium external

Modbus: 43189

-EP1-QN11

Mixing valve, addition

See the valve’s manual for a port description.

Modbus: 43098

-EP1-RM1

Non-return valve

-EP1-CT1

District heating

Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP

Cetetherm AB
Tel: +46 457-755 92
E-mail: info.nordic@cetetherm.com

-EP1-CT2

District heating

Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP

Cetetherm AB
Tel: +46 457-755 92
E-mail: info.nordic@cetetherm.com

-EP1-CT3

District heating

Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP

Cetetherm AB
Tel: +46 457-755 92
E-mail: info.nordic@cetetherm.com

-EP1-QM40

Shut off valve

-EP10

Shunt controlled brine

-EP10-AA25

AXC module

Included in AXC 40

067 060

-EP10-BT26

Temperature sensor, brine in

Included in AXC 40

Modbus: 40179

-EP10-QN41

Shunt valve, brine

Modbus: 44778

See the valve’s manual for a port description.

-EP10-EP10

Heat exchanger

-EP12

Ground water system

-EP12-AA25

AXC module, groundwater

Included in AXC 40

067 060

-EP12-EP4

Groundwater exchanger

-EP12-GP3

Circulation pump, groundwater

Modbus: 44756

-EP12-HQ40

Particle filter, groundwater

-EP21

Heating system 2

ECS 40/41

067 287 / 067 288

-EP21-AA25

AXC module, heating system 2

Included in ECS 40/41

-EP21-BT2

Supply temperature sensor, heating system 2

Included in ECS 40/41

Modbus: 40007

-EP21-BT3

Return line sensor, heating system 2

Included in ECS 40/41

Modbus: 40129

-EP21-GP10

Circulation pump, heating system 2

Included in ECS 40/41

Modbus: 44746

-EP21-QN25

Shunt valve, heating system 2

Included in ECS 40/41

Modbus: 43095

See the valve’s manual for a port description.

-EP21-RM1

Non-return valve

-EP22

Heating system 3

ECS 40/41

067 287 / 067 288

K

Climate system 3

AXC 40

067 304

-EP22-AA25

AXC module, heating system 3

Included in ECS 40/41

-EP22-BT2

Supply temperature sensor, heating system 3

Included in ECS 40/41

Modbus: 40006

-EP22-BT3

Return line sensor, heating system 3

Included in ECS 40/41

Modbus: 40128

-EP22-GP10

Circulation pump, heating system 3

Included in ECS 40/41

Modbus: 44745

-EP22-QN25

Shunt valve, heating system 3

Included in ECS 40/41

Modbus: 43094

See the valve’s manual for a port description.

-EP22-RM1

Non-return valve

-EP26

HRV unit

ERS

-EP30

Solar heating system

SCA 35

067 245

-EP30-AA25

AXC module

Included in SCA

-EP8

Solar panels

-EP30-EP9

Exchanger, solar

-EP30-GP10

Circulation pump

Modbus: 43183

-EP44

Cooling system 1

AXC 40

067 296

-EP44-AA25

AXC module, cooling system 1

Included in AXC 40

-EP44-BT2

Supply temperature sensor, cooling system 1

Modbus: 40007

-EP44-BT3

Return line sensor, cooling system 1

Modbus: 40129

-EP44-BT64

Flow temperature sensor, cooling

Included in AXC 40

Modbus: 40045

-EP44-BT65

Return line sensor, cooling

Included in AXC 40

Modbus: 40046

-EP44-GP10

Circulation pump, cooling system 1

Included in AXC 40

Modbus: 44754

-EP44-GP10

Circulation pump, cooling system 1

Modbus: 44754

-EP44-QN18

Shunt valve, cooling system 1

Included in AXC 40

Modbus: 44278

See the valve’s manual for a port description.

-EP44-QN18

Shunt valve, cooling system 1

Modbus: 44278

See the valve’s manual for a port description.

-EP44-RM1

Non-return valve

Included in AXC 40

-EP44-RM1

Non-return valve

-EP45

Cooling system 1

-EP45-AA25

AXC module, cooling system 1

Included in AXC 40

067 060

-EP45-GP10

Circulation pump, cooling system 1

Modbus: 44754

-EP45-QN12

Reversing valve, cooling

Modbus: 44751

See the valve’s manual for a port description.

-EP25

Passive cooling system

AXC 40

067 296

-EP25-AA25

AXC module, cooling

Included in AXC 40

-EP25-BT64

Temperature sensor, cooling flow line

Included in AXC 40

Modbus: 40045

-EP25-BT65

Temperature sensor, cooling return line

Included in AXC 40

Modbus: 40046

-EP25-EP13

Supply air coil/fan coil

-EP25-GP13

Circulation pump, cooling

Included in AXC 40

Modbus: 44754

-EP25-QN18

Mixing valve, cooling

Included in AXC 40

Modbus: 44278

See the valve’s manual for a port description.

-EP25-RM1

Non-return valve

-EQ1

Active cooling.

NIBE ACS 45

067 195

-EQ1-AA25

AXC module, cooling

Included in NIBE ACS 45

-EQ1-BP6

Pressure gauge, brine

-EQ1-BT57

Temperature sensor, collector

Included in NIBE ACS 45

Modbus: 40155

-EQ1-BT64

Flow temperature sensor, cooling

Included in NIBE ACS 45

Modbus: 40045

-EQ1-BT75

Temperature sensor, flow line after heat dump

Included in NIBE ACS 45

Modbus: 40156

-EQ1-CM3

Expansion vessel, brine

-EQ1-EP6

Heat exchanger

-EQ1-EP18

Coolant radiator

-EQ1-FL3

Safety valve, brine

-EQ1-GP10

Circulation pump

Modbus: 44322

-EQ1-GP12

Circulation pump

Included in NIBE ACS 45

Modbus: 44322

-EQ1-GP14

Circulation pump for heat dump

-EQ1-GP20

Circulation pump, heat dump

Modbus: 44752

-EQ1-QM40.1

Shut-off valve

-EQ1-QM40.2

Shut-off valve

-EQ1-QN12

Reversing valve, cooling

Modbus: 44751

See the valve’s manual for a port description.

-EQ1-QN18

Shunt valve, cooling shunt

Modbus: 44278

See the valve’s manual for a port description.

-EQ1-QN36

Shunt valve, heating shunt

Modbus: 44277

See the valve’s manual for a port description.

-EQ1-RM1

Non-return valve, heat dump

-EQ1-RM2

Non-return valve, heat dump

-EQ1-RM3

Non-return valve, heat dump

-GC1

Solar panels

NIBE PV

-QZ1

Hot water circulation (HWC)

-QZ1-AA25

AXC module

Included in AXC 40

067 060

-QZ1-BT70

Supply temperature sensor, HWC

Included in AXC 40

Modbus: 40147

-QZ1-BT82

Return line sensor, HWC

Included in AXC 40

Modbus: 40625

-QZ1-FQ3

Mixer valve, HWC

-QZ1-GP11

Circulation pump, HWC

Modbus: 43180

-QZ1-QN2

4-way valve, HWC

See the valve’s manual for a port description.

-QZ1-RM1

Non-return valve, HWC

-QZ1-RN1

Trim valve, HWC

-QZ1-RN4

Trim valve, HWC

-QZ20

Filling kit

KB 25/ KB 32

KB 25 (max. 12 kW), KB 32 (max. 30 kW)

-QM33

Shut off valve, brine flow

-XL27

Filling brine

-XL28

Filling brine

-FL2

Miscellaneous

-BP5

Pressure gauge, heating medium

-BP6

Pressure gauge, brine

-CM1

Expansion vessel, heating medium

-CM2

Level vessel, brine

-CM3

Expansion vessel, brine

Expansion vessel in closed system

-CM4

Expansion vessel, hot water

Included in NIBE F1145/F1155

-CP10

Buffer vessel

UKV

Size varies depending on the dimensioning of hot water

-CP10.1

Buffer vessel

UKV

Size varies depending on heat pump and system volume

-CP10.2

Buffer vessel, cooling

UKV

Condensation-insulated vessels for cooling

Size varies depending on heat pump and system volume

-CP10.3

Buffer vessel

UKV

Size varies depending on the dimensioning of hot water

-FL1

Safety valve, hot water

-FL2

Safety valve, heating medium

-FQ1

Mixing valve

Thermal

-RM1

Non-return valve

-RM1.1

Non-return valve

-RM1.2

Non-return valve

-RM1.3

Non-return valve

-RM2

Non-return valve

-RM3

Non-return valve

-RN1.1

Trim valve

-RN1.2

Trim valve

-RN1.3

Trim valve

-RN2.1

Trim valve

-RN2.2

Trim valve

-RN3.1

Trim valve

-RN3.2

Trim valve

-RN4.1

Trim valve

-RN4.2

Trim valve

-RN5.1

Trim valve

-RN5.2

Trim valve

-QM1

Drain valve, heating medium

-QM30

Shut-off valve, hot water

-QN17

Pressure reduction valve

-QN44

Shut off valve

-WM3

Tundish, cold water

Included in NIBE F1145/F1155

-WM4

Tundish, T&P valve

Included in NIBE F1145/F1155

Designations according to standard EN 81346-2.