Protective and safety equipment as well as components that facilitate servicing (e.g. non-return valves, safety valves, overflow valves, shut-off valves) must be installed in accordance with national regulations and standards.
Pay attention to supplementary information for the following components:
The compressor in a F1245 is an on/off type. The compressor’s full power is routed to heating, hot water, cooling or pool heating. If the power is not sufficient for the heating demand, additional heating is connected automatically.
The compressor in a F1255 is inverter-controlled. The compressor’s power is adjusted according to the demand and routed to heating, hot water, cooling or pool heating. If the power is not sufficient for the heating demand, additional heating is connected automatically.
F1245/F1255 is supplied with a heating control system, which means that the heating supply to the house takes place according to selected settings. When connecting to a system with thermostats on all radiators (or underfloor heating coils), either a bypass valve must be fitted or some of the thermostats must be removed to ensure there is sufficient flow. For more information about heat production, see the Installer Manual.
When there is demand for hot water, F1245/F1255 prioritises this and switches to hot water mode. There is no heat production in this mode.
If the hot water temperature exceeds 60 °C, the installation must be supplemented with a mixing valve.
For more information about hot water production, see the manual for F1245/F1255.
Passive cooling, cooling function without the compressor running, is achieved by connecting a cooling system to the heat pump’s brine circuit. The collector’s low temperature can be utilised for comfort cooling.
When cooling is required (activated from the outdoor temperature sensor and any room sensor) the circulation pump is activated and the shunt valve provides the correct supply temperature.
With the AXC 40 accessory (one for each accessory function that is to be used), an external heating medium pump can be connected to F1245/F1255, if the alarm relay (the AUX output) is activated for another function. If the AUX output cannot be used for an external heating medium pump, the function is available in:
addition
shunt-controlled additional heat
pool
This function requires the ECS 40/41 accessory. Shunt valve, supply and return line sensors as well as circulation pump are connected to other heating circuits with a lower temperature demand (e.g. underfloor heating system). The temperature in the extra heating system follows the selected curve slope and offset setting. Up to 8 extra heating systems can be connected to the installation. For further information, see the Installer Manual for the accessory. See the valve’s manual for the port description.
If there is a large pressure drop over the brine side, an external brine pump may be required.
This function requires the accessory ERS, which is controlled by F1245/F1255. ERS recovers the energy from the ventilation air and supplies it to the property.
For further information, see the Installer Manual for the accessory.
This function requires the accessory NIBE FLM. NIBE FLM is an exhaust air module that is controlled by F1245/F1255. NIBE FLM recovers energy from the exhaust air and supplies it to the brine.
For further information, see the Installer Manual for the accessory.
This connection enables the use of ground water as heat source. The ground water is pumped up to an intermediate heat exchanger. An intermediate heat exchanger is used to protect the heat pump's exchanger from dirt and freezing. The water is released into a buried filtration unit or a drilled well.
The ground water pump runs at the same time as the brine pump.
With the accessory ACS 45, a separate cooling system can be connected via a reversing valve. ACS 45 allows both heat and cooling production independently of each other.
Passive cooling occurs without the compressor running, active cooling occurs when the compressor is running. The cooling system is connected to the heat pump’s brine circuit.
When cooling is required (activated from the outdoor temperature sensor EB100-BT1 and room sensor EB100-BT50, where applicable), the shunt valve EQ1-QN18 and the circulation pump EQ1-GP10 are activated.
See the valve’s manual for a port description.
If there is excess heat, this is dumped to a coolant radiator or to the collector.
This function requires the AXC 40 accessory. The cooling system is connected to the heat pump brine circuit, through which cooling is supplied from the collector via the circulation pump and the shunt valve.
When cooling is required (activated from the outdoor temperature sensor EB100-BT1 and room sensor EB100-BT50, where applicable), EP44-QN18 and the circulation pump EP44-GP10 are activated.
The shunt valve regulates so that the cooling sensor reaches the current set point value corresponding to the outdoor temperature and the set min. value for the cooling temperature (to prevent condensation).
If the NIBE FLM accessory is installed with AXC 40, the cooling output will be reduced.
See the valve’s manual for a port description.
With the POOL 40 accessory, the heat pump can be used to heat a pool.
For further information, see the Installer Manual for the accessory.
In order to fill the system easily with brine, the accessories KB 25/KB 32 are available. These consist of a filterball, reversing valve and shut-off/filling valves, and are available in two sizes.
KB 25 for heat pump sizes up to 12 kW and KB 32 for heat pump sizes up to 30 kW.
This function requires the NIBE PV accessory. NIBE PV is a complete modular system with solar panels in several basic outputs. NIBE PV is connected to F1245/F1255, which adjusts to the generated solar electricity produced.
For further information, see the Installer Manual for the accessory.
Additional heat that requires the AXC 40 accessory. AXC 40 via a control signal, can control step-controlled additional heat. The additional heat is used for heat production.
For further information, see the Installer Manual for the accessory.
Additional heat that requires the AXC 40 accessory. AXC 40 via a control signal, can control additional heat, which can also be prioritised. The additional heat is used for heat production.
For further information, see the Installer Manual for the accessory.
A 3-pipe-connected buffer vessel is used when the system volume in the climate system is below the minimum recommended volume for the heat pump and/or the flow in the heating system is restricted without control.
For further information, see the Installer Manual for the accessory.
A circulation pump can be controlled by F1245/F1255 to circulate the hot water. The circulating water must have a temperature that prevents bacterial growth and scalding, and national standards must be satisfied. See the appropriate Installer Manual for more information.
Designation |
Name |
Specification |
Part No. |
Comments |
---|---|---|---|---|
-AA35-BT1 |
Outside sensor |
Included in F1245/F1255 |
||
-AA35-BT6 |
Controlling hot water sensor |
Included in F1245/F1255 |
||
-AA35-BT7 |
Display hot water sensor |
Included in F1245/F1255 |
||
-AA35-BT25 |
External supply temperature sensor |
Included in F1245/F1255 |
||
-AA35-BT63 |
External supply temperature sensor before QN10 |
Included in F1245/F1255 |
||
-AA35-BT71 |
External return line sensor |
Included in F1245/F1255 |
||
-AA35-GP10 |
External heating medium pump |
|||
-AA35-GP12 |
Charge pump for EB101 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-GP12.1 |
Charge pump for EB101 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-GP12.2 |
Charge pump for EB102 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-GP12.3 |
Charge pump for EB103 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-GP12.4 |
Charge pump for EB104 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-GP12.5 |
Charge pump for EB105 |
NIBE CPD 11 |
067 321 / 067 320 |
|
-AA35-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-AA35-QN43 |
Bypass valve, cooling operation |
|||
-EB100 |
Heat pump system (master unit) |
NIBE F1245/F1255 |
||
-EB100F1355 |
Heat pump system (master unit) |
F1255 |
||
-EB100F1330 |
Heat pump system (master unit) |
F1245 |
||
-EB100F1360 |
Heat pump system (master unit) |
? |
||
-EP14 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-EP15 |
Cooling module |
See the Installer Manual for more information about the relevant cooling module. |
||
-EB100-BT1 |
Outside sensor |
Included in F1245/F1255 |
||
-BT1 |
Outside sensor |
Included in F1245/F1255 |
||
-BT6 |
Controlling hot water sensor |
Included in F1245/F1255 |
||
-EB100-BT6 |
Controlling hot water sensor |
Included in F1245/F1255 |
||
-EB100-BT7 |
Display hot water sensor |
Included in F1245/F1255 |
||
-BT7 |
Display hot water sensor |
Included in F1245/F1255 |
||
-EB100-BT25 |
External supply temperature sensor |
|||
-BT25 |
External supply temperature sensor |
|||
-EB100-BT71 |
External return line sensor |
|||
-BT71 |
External return line sensor |
|||
-EB100-CM4 |
Expansion vessel, hot water |
Included in F1245/F1255 |
||
-EB100-FL1 |
Safety valve, hot water |
Included in F1245/F1255 |
||
-EB100-FL5 |
T&P valve |
Included in F1245/F1255 |
||
-EB100-FL6 |
Vacuum valve |
Included in F1245/F1255 |
||
-EB100-FQ1 |
Mixing valve |
Included in F1245/F1255 |
||
-EB100-QN17 |
Pressure reduction valve |
Included in F1245/F1255 |
||
-EB100-QM30 |
Shut-off valve |
|||
-EB100-RM1 |
Non-return valve |
|||
-EB100-WM3.1 |
Tundish, cold water |
Included in F1245/F1255 |
||
-EB100-WM3.2 |
Tundish, T&P valve |
Included in F1245/F1255 |
||
-EB100-GP7 |
External brine pump |
|||
-EB100-GP10 |
External heating medium pump |
|||
-GP10 |
External heating medium pump |
|||
-EB100-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-QN10 |
Reversing valve, heating/hot water |
See the valve’s manual for a port description. |
||
-EP4 |
Heat exchanger, groundwater |
|||
-FL3 |
Safety valve, brine |
Included in F1245/F1255 |
||
-FL3 |
Safety valve, brine |
Included in F1245/F1255 |
||
-FL311xx |
Safety valve, brine |
Included in F1255/F1245/F1245/F1255 |
||
-FL10 |
Safety valve, brine |
|||
-FL10-0 |
Safety valve, brine |
|||
-FL11-0 |
Safety valve, brine |
|||
-FL12-0 |
Safety valve, heating medium |
|||
-FL13-0 |
Safety valve, heating medium |
|||
-HQ1-F1360 |
Particle filter, brine |
Included in ? |
||
-HQ1-F1330 |
Particle filter, brine |
Included in F1245 |
||
-HQ2-F1360 |
Particle filter, brine |
Included in ? |
||
-HQ2-F1330 |
Particle filter, brine |
Included in F1245 |
||
-HQ3-F1360 |
Particle filter, heating medium |
Included in ? |
||
-HQ3-F1330 |
Particle filter, heating medium |
Included in F1245 |
||
-HQ4-F1360 |
Particle filter, heating medium |
Included in ? |
||
-HQ4-F1330 |
Particle filter, heating medium |
Included in F1245 |
||
-GP16-0 |
Circulation pump, brine |
Included in F1245 40/60 |
||
-QN11 |
Shuttle valve |
|||
-QM12 |
Filling valve, brine |
|||
-QM21 |
Vent valve, brine |
|||
-QM31 |
Shut-off valve, heating medium supply line |
|||
-QM32 |
Shut-off valve, heating medium return line |
|||
-QM33 |
Shut-off valve, brine in |
|||
-QM34 |
Shut off valve, brine out |
|||
-QM40 |
Shut-off valve |
|||
-QM42 |
Shut-off valve, brine in |
|||
-QM50-0 |
Shut off valve, brine |
|||
-QM51-0 |
Shut off valve, brine |
|||
-QM52-0 |
Shut off valve, brine |
|||
-QM53-0 |
Shut off valve, brine |
|||
-QM54-0 |
Shut-off valve, heating medium |
|||
-QM55-0 |
Shut-off valve, heating medium |
|||
-QM56-0 |
Shut-off valve, heating medium |
|||
-QM57-0 |
Shut-off valve, heating medium |
|||
-QZ2 |
Filterball, heating medium |
Included in F1255 |
The F1245 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ2.1-0 |
Filterball, heating medium |
Included in F1255 |
||
-QZ2.2-0 |
Filterball, heating medium |
Included in F1255 |
||
-QZ2.3-0 |
Filterball, heating medium |
Included in F1255 |
||
-QZ2.4-0 |
Filterball, heating medium |
Included in F1255 |
||
-QZ3 |
Filterball, brine |
Included in F1255 |
The F1245 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ4 |
Filterball, heating medium |
Included in F1255 |
The F1245 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-QZ5 |
Filterball, heating medium |
Included in F1255 |
The F1245 includes a particle filter, which should be supplemented with a shut-off valve. |
|
-RM10-F1360 |
Non-return valve |
|||
-RM10-F1330 |
Non-return valve |
Included in F1245 |
||
-RM10-F1355 |
Non-return valve |
Included in F1255 |
||
-RM11-F1360 |
Non-return valve |
Included in ? |
||
-RM11-F1330 |
Non-return valve |
Included in F1245 |
||
-RM11-F1355 |
Non-return valve |
Included in F1255 |
||
-RM12-F1360 |
Non-return valve |
Included in ? |
||
-RM12-F1330 |
Non-return valve |
Included in F1245 |
||
-RM12-F1355 |
Non-return valve |
Included in F1255 |
||
-RM13-F1360 |
Non-return valve |
Included in ? |
||
-RM13-F1330 |
Non-return valve |
Included in F1245 |
||
-RM13-F1355 |
Non-return valve |
Included in F1255 |
||
-RN20 |
Trim valve |
|||
-RN21 |
Trim valve |
|||
-EB10011xx |
Heat pump system (master unit) |
F1255 |
||
-EB10012xx |
Heat pump system (master unit) |
F1245 |
||
-EB10013xx |
Heat pump system (master unit) |
? |
||
-BT111xx |
Outside sensor |
Included in F1255 |
||
-BT112xx |
Outside sensor |
Included in F1245 |
||
-BT113xx |
Outside sensor |
Included in ? |
||
-QZ311xx |
Filterball, brine |
Included in F1255 |
||
-QZ312xx |
Filterball, brine |
Included in F1245 |
||
-EB100-BT2511xx |
External supply temperature sensor |
Included in F1255/F1245/F1255 |
||
-EB100-BT7111xx |
External return line sensor |
Included in F1255/F1245/F1255 |
||
-EB100-QZ211xx |
Filterball, heating medium |
Included in F1255 |
||
-EB100-QZ212xx |
Filterball, heating medium |
Included in F1245 |
||
-EB101F1355 |
Heat pump system 1 |
F1255 |
||
-EB101F1330 |
Heat pump system 1 |
F1245 |
||
-EB101F1360 |
Heat pump system 1 |
? |
||
-EB101 |
Heat pump system 1 |
|||
-GP16-1 |
Circulation pump, brine |
Included in F1245 40/60 |
||
-EB101-FL10 |
Safety valve, brine |
|||
-FL10-1 |
Safety valve, brine |
|||
-FL11-1 |
Safety valve, brine |
|||
-FL12-1 |
Safety valve, heating medium |
|||
-FL13-1 |
Safety valve, heating medium |
|||
-HQ1-1361 |
Particle filter, brine |
Included in ? |
||
-HQ1-F1330-1 |
Particle filter, brine |
Included in F1245 |
||
-HQ2-1362 |
Particle filter, brine |
Included in ? |
||
-HQ2-F1330-1 |
Particle filter, brine |
Included in F1245 |
||
-HQ3-1362 |
Particle filter, heating medium |
Included in ? |
||
-HQ3-F1330-1 |
Particle filter, heating medium |
Included in F1245 |
||
-HQ4-1362 |
Particle filter, heating medium |
Included in ? |
||
-HQ4-F1330-1 |
Particle filter, heating medium |
Included in F1245 |
||
-EB101-QM1 |
Drain valve, heating medium |
|||
-EB101-QM40 |
Shut-off valve, heating medium |
|||
-QM50-1 |
Shut off valve, brine |
|||
-QM51-1 |
Shut off valve, brine |
|||
-QM52-1 |
Shut off valve, brine |
|||
-QM53-1 |
Shut off valve, brine |
|||
-QM54-1 |
Shut-off valve, heating medium |
|||
-QM55-1 |
Shut-off valve, heating medium |
|||
-QM56-1 |
Shut-off valve, heating medium |
|||
-QM57-1 |
Shut-off valve, heating medium |
|||
-QZ2.1-1 |
Filterball, brine |
Included in F1255 |
||
-QZ2.2-1 |
Filterball, brine |
Included in F1255 |
||
-QZ2.3-1 |
Filterball, heating medium |
Included in F1255 |
||
-QZ2.4-1 |
Filterball, heating medium |
Included in F1255 |
||
-RM10-F1361 |
Non-return valve |
|||
-RM10-F1330-1 |
Non-return valve |
Included in F1245 |
||
-RM10-F1355-1 |
Non-return valve |
Included in F1255 |
||
-RM11-F1361 |
Non-return valve |
Included in ? |
||
-RM11-F1330-1 |
Non-return valve |
Included in F1245 |
||
-RM11-F1355-1 |
Non-return valve |
Included in F1255 |
||
-RM12-F1361 |
Non-return valve |
Included in ? |
||
-RM12-F1330-1 |
Non-return valve |
Included in F1245 |
||
-RM12-F1355-1 |
Non-return valve |
Included in F1255 |
||
-RM13-F1361 |
Non-return valve |
Included in ? |
||
-RM13-F1330-1 |
Non-return valve |
Included in F1245 |
||
-RM13-F1355-1 |
Non-return valve |
Included in F1255 |
||
-EB102 |
Heat pump system 2 |
|||
-EB102F1355 |
Heat pump system 2 |
F1255 |
||
-EB102F1330 |
Heat pump system 2 |
F1245 |
||
-EB102F1360 |
Heat pump system 2 |
? |
||
-GP16-2 |
Circulation pump, brine |
Included in F1245 40/60 |
||
-FL10-2 |
Safety valve, brine |
|||
-FL11-2 |
Safety valve, brine |
|||
-FL12-2 |
Safety valve, heating medium |
|||
-FL13-2 |
Safety valve, heating medium |
|||
-HQ1-F1362 |
Particle filter, brine |
Included in ? |
||
-HQ1-F1330-2 |
Particle filter, brine |
Included in F1245 |
||
-HQ2-F1362 |
Particle filter, brine |
Included in ? |
||
-HQ2-F1330-2 |
Particle filter, brine |
Included in F1245 |
||
-HQ3-F1362 |
Particle filter, heating medium |
Included in ? |
||
-HQ3-F1330-2 |
Particle filter, heating medium |
Included in F1245 |
||
-HQ4-F1362 |
Particle filter, heating medium |
Included in ? |
||
-HQ4-F1330-2 |
Particle filter, heating medium |
Included in F1245 |
||
-EB102-QM1 |
Drain valve, heating medium |
|||
-EB102-QM40 |
Shut-off valve, heating medium |
|||
-QM50-2 |
Shut off valve, brine |
|||
-QM51-2 |
Shut off valve, brine |
|||
-QM52-2 |
Shut off valve, brine |
|||
-QM53-2 |
Shut off valve, brine |
|||
-QM54-2 |
Shut-off valve, heating medium |
|||
-QM55-2 |
Shut-off valve, heating medium |
|||
-QM56-2 |
Shut-off valve, heating medium |
|||
-QM57-2 |
Shut-off valve, heating medium |
|||
-QZ2.1-2 |
Filterball, brine |
Included in F1255 |
||
-QZ2.2-2 |
Filterball, brine |
Included in F1255 |
||
-QZ2.3-2 |
Filterball, heating medium |
Included in F1255 |
||
-QZ2.4-2 |
Filterball, heating medium |
Included in F1255 |
||
-RM10-F1362 |
Non-return valve |
|||
-RM10-F1330-2 |
Non-return valve |
Included in F1245 |
||
-RM10-F1355-2 |
Non-return valve |
Included in F1255 |
||
-RM11-F1362 |
Non-return valve |
Included in ? |
||
-RM11-F1330-2 |
Non-return valve |
Included in F1245 |
||
-RM11-F1355-2 |
Non-return valve |
Included in F1255 |
||
-RM12-F1362 |
Non-return valve |
Included in ? |
||
-RM12-F1330-2 |
Non-return valve |
Included in F1245 |
||
-RM12-F1355-2 |
Non-return valve |
Included in F1255 |
||
-RM13-F1362 |
Non-return valve |
Included in ? |
||
-RM13-F1330-2 |
Non-return valve |
Included in F1245 |
||
-RM13-F1355-2 |
Non-return valve |
Included in F1255 |
||
-EB103 |
Heat pump system 3 |
|||
-EB103-AA25 |
AXC module |
Included in AXC 40 |
067 304 |
|
-EB103-QM1 |
Drain valve, heating medium |
|||
-EB103-QM40 |
Shut-off valve, heating medium |
|||
-EB104 |
Heat pump system 4 |
|||
-EB104-QM1 |
Drain valve, heating medium |
|||
-EB104-QM40 |
Shut-off valve, heating medium |
|||
-EB105-AA25 |
AXC module |
Included in AXC 40 |
067 304 |
|
-EB105-QM1 |
Drain valve, heating medium |
|||
-EB105-QM40 |
Shut-off valve, heating medium |
|||
XL1 |
Heating medium connection, supply |
|||
XL2 |
Heating medium connection, return |
|||
0.1 |
Ventilation unit 1 |
|||
-RN1 |
Trim valve |
|||
-AZ10 |
Exhaust air module |
NIBE FLM |
067 627 |
|
-AZ11 |
Ventilation module |
|||
-AZ10-RM1 |
Non-return valve |
Included in NIBE FLM |
||
-AZ10-RN11 |
Control valve |
Included in NIBE FLM |
||
-AZ10-RN1 |
Trim valve |
Included in NIBE FLM |
||
0 |
Exhaust air module |
NIBE F135 |
067 075 |
|
0 |
Exhaust air module |
NIBE S135 |
067 075 |
|
-AZ30 |
Ventilation unit |
NIBE ERS |
||
-CL11 |
Pool system |
POOL 40 |
067 062 067 193 |
|
-CL11-AA25 |
AXC module, pool |
Included in POOL 40 |
||
-CL11-BT25 |
External supply temperature sensor |
Included in POOL 40 |
||
-CL11-BT51 |
Pool sensor |
Included in POOL 40 |
||
-CL11-EP5 |
Exchanger, pool |
|||
-CL11-GP9 |
Circulation pump, pool |
|||
-CL11-GP12 |
Charge pump, pool |
Included in POOL 40 |
||
-CL11-HQ4 |
Particle filter, pool |
|||
-CL11-QN19 |
Three way valve, pool |
Included in POOL 40 See the valve’s manual for a port description. |
Max. 17 kW |
|
-CL11-RM1 |
Non-return valve, pool |
|||
-CL12 |
Pool system 2 |
POOL 40 |
067 062 067 193 |
|
-CL12-AA25 |
AXC module, pool |
Included in POOL 40 |
||
-CL12-BT25 |
External supply temperature sensor |
Included in POOL 40 |
||
-CL12-BT51 |
Pool sensor |
Included in POOL 40 |
||
-CL12-EP5 |
Exchanger, pool |
|||
-CL12-GP9 |
Circulation pump, pool |
|||
-CL12-GP12 |
Charge pump, pool |
Included in POOL 310 |
||
-CL12-HQ4 |
Particle filter, pool |
|||
-CL12-QN19 |
Three way valve, pool |
Included in POOL 40 See the valve’s manual for a port description. |
||
-CL12-RM1 |
Non-return valve |
Included in POOL 40 |
||
-CP1 |
Storage tank |
|||
-CP1.1 |
Storage tank |
|||
-CP1.1-CM4 |
Expansion vessel, hot water |
Included in accumulator tank |
||
-CP1-CM4 |
Expansion vessel, hot water |
Included in accumulator tank |
||
-CP1.1-FL1 |
Safety valve, hot water |
|||
-CP1-FL1 |
Safety valve, hot water |
|||
-CP1.1-FL5 |
T&P valve |
Included in accumulator tank |
||
-CP1.2-FL5 |
T&P valve |
Included in accumulator tank |
||
-CP1-FL5 |
T&P valve |
Included in accumulator tank |
||
-CP1.1-FL6 |
Vacuum valve |
Included in accumulator tank |
||
-CP1.2-FL6 |
Vacuum valve |
Included in accumulator tank |
||
-CP1-FL6 |
Vacuum valve |
Included in accumulator tank |
||
-CP1.1-FQ1 |
Thermal mixing valve |
|||
-CP1-FQ1 |
Thermal mixing valve |
|||
-CP1.1-QN17 |
Pressure reduction valve |
Included in accumulator tank |
||
-CP1-QN17 |
Pressure reduction valve |
Included in accumulator tank |
||
-CP1.1-QM30 |
Shut-off valve |
|||
-CP1-QM30 |
Shut-off valve |
|||
-CP1.1-QM40 |
Shut off valve |
Included in accumulator tank |
||
-CP1.2-QM40 |
Shut off valve |
Included in accumulator tank |
||
-CP1.1-RM1 |
Non-return valve |
|||
-CP1-RM1 |
Non-return valve |
|||
-CP1.1-WM3.1 |
Tundish, cold water |
Included in accumulator tank |
||
-CP1-WM3.1 |
Tundish, cold water |
Included in accumulator tank |
||
-CP1.1-WM3.2 |
Tundish, T&P valve |
Included in accumulator tank |
||
-CP1.2-WM3.2 |
Tundish, T&P valve |
Included in accumulator tank |
||
-CP1-WM3.2 |
Tundish, T&P valve |
Included in accumulator tank |
||
-CP1.1-RN1.1 |
Trim valve |
|||
-CP1-RN1.1 |
Trim valve |
|||
-CP1-RN1 |
Trim valve |
|||
-CP1.1-RN1.2 |
Trim valve |
|||
-CP1-RN1.2 |
Trim valve |
|||
-CP1.2 |
Storage tank |
|||
-CP1.2-RN1.1 |
Trim valve |
|||
-CP1.2-RN1.2 |
Trim valve |
|||
-RN60 |
Trim valve |
|||
-RN61 |
Trim valve |
|||
-CP2 |
Water heater |
|||
-CP2-FQ1 |
Thermal mixing valve |
Part no. 624 922 |
||
-CP4 |
Additional water heater |
|||
-CP10.4 |
Tanks |
|||
-CP10.4 |
Storage tank |
UKV 20-750 / UKV 20-1000 |
Size varies depending on the dimensioning of hot water |
|
-CP10.5 |
Storage tank |
UKV 20-750 / UKV 20-1000 |
Size varies depending on the dimensioning of hot water |
|
-CP10.6 |
Storage tank |
UKV 20-750 / UKV 20-1000 |
Size varies depending on the dimensioning of hot water |
|
-CP10.7 |
Storage tank |
UKV 20-750 / UKV 20-1000 |
Size varies depending on the dimensioning of hot water |
|
-EB1 |
Step-controlled additional heat/electric boiler |
|||
-EB1-AA25 |
AXC module |
Included in AXC 40 |
067 060 |
|
-EB1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 40 |
||
-EB1-BT52 |
Boiler sensor |
Included in AXC 40 |
||
-EB1-CM5 |
Closed expansion vessel, heating medium |
|||
-EB1-EP7 |
District heating exchanger |
|||
-EB1-FL2 |
Safety valve, heating medium |
|||
-EB1-GP10 |
Circulation pump, heating medium external |
|||
-EB1-QM40 |
Shut-off valve |
|||
-EB1-QM41 |
Shut-off valve |
|||
-EB1-QN11 |
Shuttle valve |
See the valve’s manual for a port description. |
||
-EB1-RM5 |
Non-return valve |
|||
-RN1 |
Trim valve |
|||
-EB2 |
External electrical backup |
|||
-EB3 |
Immersion heater in tank |
with junction box K11 |
IU 3 kW: 218 009 IU 6 kW: 218 011 IU 9 kW: 218 003 018 893 |
|
-EB3-QA1 |
Auxiliary relay |
HR 10 |
067 309 |
|
-EB15 |
Indoor module |
F1245/F1255 |
||
-EB15-BT1 |
Outside sensor |
Included in F1245/F1255 |
||
-EB15-BT25 |
External supply temperature sensor |
Included in AXC 40 |
||
-EB15-BT25_extcp |
External supply temperature sensor |
|||
-EB15-CM4 |
Expansion vessel, hot water |
|||
-EB15-GP10 |
Circulation pump, heating medium external |
|||
-EB15-FL1 |
Safety valve, hot water |
|||
-EB15-RM2 |
Non-return valve |
|||
-EB15-QM30 |
Shut-off valve, hot water |
|||
-EB15-WM4 |
Tundish, T&P valve |
Included in F1245/F1255 |
||
XL |
XL connections |
|||
1 |
Heating medium connection, supply |
|||
2 |
Heating medium connection, return |
|||
3 |
Cold water connection |
|||
4 |
Hot water connection |
|||
5 |
Hot water circulation connection |
|||
6 |
Brine connection, supply |
|||
7 |
Brine connection, return |
|||
8 |
Docking connection, supply (from heat pump) |
|||
9 |
Docking connection, return (to heat pump) |
|||
13 |
Solar heat connection, supply |
|||
14 |
Solar heat connection, return |
|||
18 |
Docking connection, supply (high temp) |
|||
19 |
Docking connection, return (high temp) |
|||
29 |
T&Pvalve |
|||
30 |
Expansion vessel connection |
|||
36 |
Heating medium connection, supply |
|||
37 |
Heating medium connection, return |
|||
39 |
Docking connection, pool |
|||
-EM1 |
Shunt controlled additional heat |
|||
-EM1-AA25 |
AXC module |
Included in AXC 40 |
067 060 |
|
-EM1-QN11 |
Shunt valve for additional heat |
|||
-EM1-BT52 |
Boiler sensor |
Included in AXC 40 |
||
-EM1-BT25 |
Supply temperature sensor, heating medium, external |
Included in AXC 40 |
||
-EM1-GP10 |
External heating medium pump |
|||
-EM1/EB1 |
Electric boiler, wood boiler, pellet boiler, oil boiler or district heating |
|||
-EM1/EB1-GP10 |
Circulation pump |
|||
-EP1 |
District heating |
|||
-EP1-AA25 |
AXC module |
Included in AXC 40 |
067 060 |
|
-EP1-BT25 |
External supply temperature sensor |
Included in AXC 40 |
||
-EP1-BT52 |
Boiler sensor |
Included in AXC 40 |
||
-EP1-CM5 |
Closed expansion vessel, heating medium |
|||
-EP1-EP3 |
District heating exchanger, hot water |
|||
-EP1-EP7 |
District heating exchanger |
|||
-EP1-FL2 |
Safety valve, heating medium |
|||
-EP1-QN11 |
Mixing valve, addition |
See the valve’s manual for a port description. |
||
-EP1-RM1 |
Non-return valve |
|||
-EP1-CT1 |
District heating |
Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP |
Cetetherm AB |
|
-EP1-CT2 |
District heating |
Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP |
Cetetherm AB |
|
-EP1-CT3 |
District heating |
Cetetherm Mini Plus VP / Midi Wall VP / Maxi VP |
Cetetherm AB |
|
-EP1-QM40 |
Shut off valve |
|||
-EP10 |
Shunt controlled brine |
|||
-EP10-AA25 |
AXC module |
Included in AXC 40 |
067 060 |
|
-EP10-BT26 |
Temperature sensor, brine in |
Included in AXC 40 |
||
-EP10-QN41 |
Shunt valve, brine |
See the valve’s manual for a port description. |
||
-EP10-EP10 |
Heat exchanger |
|||
-EP12 |
Ground water system |
|||
-EP12-AA25 |
AXC module, groundwater |
Included in AXC 40 |
067 060 |
|
-EP12-EP4 |
Groundwater exchanger |
|||
-EP12-GP3 |
Circulation pump, groundwater |
|||
-EP12-HQ40 |
Particle filter, groundwater |
|||
-EP21 |
Heating system 2 |
ECS 40/41 |
067 287 / 067 288 |
|
-EP21-AA25 |
AXC module, heating system 2 |
Included in ECS 40/41 |
||
-EP21-BT2 |
Supply temperature sensor, heating system 2 |
Included in ECS 40/41 |
||
-EP21-BT3 |
Return line sensor, heating system 2 |
Included in ECS 40/41 |
||
-EP21-GP10 |
Circulation pump, heating system 2 |
Included in ECS 40/41 |
||
-EP21-QN25 |
Shunt valve, heating system 2 |
Included in ECS 40/41 See the valve’s manual for a port description. |
||
-EP21-RM1 |
Non-return valve |
|||
-EP22 |
Heating system 3 |
ECS 40/41 |
067 287 / 067 288 |
|
K |
Climate system 3 |
AXC 40 |
067 304 |
|
-EP22-AA25 |
AXC module, heating system 3 |
Included in ECS 40/41 |
||
-EP22-BT2 |
Supply temperature sensor, heating system 3 |
Included in ECS 40/41 |
||
-EP22-BT3 |
Return line sensor, heating system 3 |
Included in ECS 40/41 |
||
-EP22-GP10 |
Circulation pump, heating system 3 |
Included in ECS 40/41 |
||
-EP22-QN25 |
Shunt valve, heating system 3 |
Included in ECS 40/41 See the valve’s manual for a port description. |
||
-EP22-RM1 |
Non-return valve |
|||
-EP26 |
HRV unit |
ERS |
||
-EP30 |
Solar heating system |
SCA 35 |
067 245 |
|
-EP30-AA25 |
AXC module |
Included in SCA |
||
-EP8 |
Solar panels |
|||
-EP30-EP9 |
Exchanger, solar |
|||
-EP30-GP10 |
Circulation pump |
|||
-EP44 |
Cooling system 1 |
AXC 40 |
067 296 |
|
-EP44-AA25 |
AXC module, cooling system 1 |
Included in AXC 40 |
||
-EP44-BT2 |
Supply temperature sensor, cooling system 1 |
|||
-EP44-BT3 |
Return line sensor, cooling system 1 |
|||
-EP44-BT64 |
Flow temperature sensor, cooling |
Included in AXC 40 |
||
-EP44-BT65 |
Return line sensor, cooling |
Included in AXC 40 |
||
-EP44-GP10 |
Circulation pump, cooling system 1 |
Included in AXC 40 |
||
-EP44-GP10 |
Circulation pump, cooling system 1 |
|||
-EP44-QN18 |
Shunt valve, cooling system 1 |
Included in AXC 40 See the valve’s manual for a port description. |
||
-EP44-QN18 |
Shunt valve, cooling system 1 |
See the valve’s manual for a port description. |
||
-EP44-RM1 |
Non-return valve |
Included in AXC 40 |
||
-EP44-RM1 |
Non-return valve |
|||
-EP45 |
Cooling system 1 |
|||
-EP45-AA25 |
AXC module, cooling system 1 |
Included in AXC 40 |
067 060 |
|
-EP45-GP10 |
Circulation pump, cooling system 1 |
|||
-EP45-QN12 |
Reversing valve, cooling |
See the valve’s manual for a port description. |
||
-EP25 |
Passive cooling system |
AXC 40 |
067 296 |
|
-EP25-AA25 |
AXC module, cooling |
Included in AXC 40 |
||
-EP25-BT64 |
Temperature sensor, cooling flow line |
Included in AXC 40 |
||
-EP25-BT65 |
Temperature sensor, cooling return line |
Included in AXC 40 |
||
-EP25-EP13 |
Supply air coil/fan coil |
|||
-EP25-GP13 |
Circulation pump, cooling |
Included in AXC 40 |
||
-EP25-QN18 |
Mixing valve, cooling |
Included in AXC 40 See the valve’s manual for a port description. |
||
-EP25-RM1 |
Non-return valve |
|||
-EQ1 |
Active cooling. |
NIBE ACS 45 |
067 195 |
|
-EQ1-AA25 |
AXC module, cooling |
Included in NIBE ACS 45 |
||
-EQ1-BP6 |
Pressure gauge, brine |
|||
-EQ1-BT57 |
Temperature sensor, collector |
Included in NIBE ACS 45 |
||
-EQ1-BT64 |
Flow temperature sensor, cooling |
Included in NIBE ACS 45 |
||
-EQ1-BT75 |
Temperature sensor, flow line after heat dump |
Included in NIBE ACS 45 |
||
-EQ1-CM3 |
Expansion vessel, brine |
|||
-EQ1-EP6 |
Heat exchanger |
|||
-EQ1-EP18 |
Coolant radiator |
|||
-EQ1-FL3 |
Safety valve, brine |
|||
-EQ1-GP10 |
Circulation pump |
|||
-EQ1-GP12 |
Circulation pump |
Included in NIBE ACS 45 |
||
-EQ1-GP14 |
Circulation pump for heat dump |
|||
-EQ1-GP20 |
Circulation pump, heat dump |
|||
-EQ1-QM40.1 |
Shut-off valve |
|||
-EQ1-QM40.2 |
Shut-off valve |
|||
-EQ1-QN12 |
Reversing valve, cooling |
See the valve’s manual for a port description. |
||
-EQ1-QN18 |
Shunt valve, cooling shunt |
See the valve’s manual for a port description. |
||
-EQ1-QN36 |
Shunt valve, heating shunt |
See the valve’s manual for a port description. |
||
-EQ1-RM1 |
Non-return valve, heat dump |
|||
-EQ1-RM2 |
Non-return valve, heat dump |
|||
-EQ1-RM3 |
Non-return valve, heat dump |
|||
-GC1 |
Solar panels |
NIBE PV |
||
-QZ1 |
Hot water circulation (HWC) |
|||
-QZ1-AA25 |
AXC module |
Included in AXC 40 |
067 060 |
|
-QZ1-BT70 |
Supply temperature sensor, HWC |
Included in AXC 40 |
||
-QZ1-BT82 |
Return line sensor, HWC |
Included in AXC 40 |
||
-QZ1-FQ3 |
Mixer valve, HWC |
|||
-QZ1-GP11 |
Circulation pump, HWC |
|||
-QZ1-QN2 |
4-way valve, HWC |
See the valve’s manual for a port description. |
||
-QZ1-RM1 |
Non-return valve, HWC |
|||
-QZ1-RN1 |
Trim valve, HWC |
|||
-QZ1-RN4 |
Trim valve, HWC |
|||
-QZ20 |
Filling kit |
KB 25/ KB 32 |
KB 25 (max. 12 kW), KB 32 (max. 30 kW) |
|
-QM33 |
Shut off valve, brine flow |
|||
-XL27 |
Filling brine |
|||
-XL28 |
Filling brine |
|||
-FL2 |
Miscellaneous |
|||
-BP5 |
Pressure gauge, heating medium |
|||
-BP6 |
Pressure gauge, brine |
|||
-CM1 |
Expansion vessel, heating medium |
|||
-CM2 |
Level vessel, brine |
|||
-CM3 |
Expansion vessel, brine |
Expansion vessel in closed system |
||
-CM4 |
Expansion vessel, hot water |
Included in F1245/F1255 |
||
-CP10 |
Buffer vessel |
UKV |
Size varies depending on the dimensioning of hot water |
|
-CP10.1 |
Buffer vessel |
UKV |
Size varies depending on heat pump and system volume |
|
-CP10.2 |
Buffer vessel, cooling |
UKV |
Condensation-insulated vessels for cooling Size varies depending on heat pump and system volume |
|
-CP10.3 |
Buffer vessel |
UKV |
Size varies depending on the dimensioning of hot water |
|
-FL1 |
Safety valve, hot water |
|||
-FL2 |
Safety valve, heating medium |
|||
-FQ1 |
Mixing valve |
Thermal |
||
-RM1 |
Non-return valve |
|||
-RM1.1 |
Non-return valve |
|||
-RM1.2 |
Non-return valve |
|||
-RM1.3 |
Non-return valve |
|||
-RM2 |
Non-return valve |
|||
-RM3 |
Non-return valve |
|||
-RN1.1 |
Trim valve |
|||
-RN1.2 |
Trim valve |
|||
-RN1.3 |
Trim valve |
|||
-RN2.1 |
Trim valve |
|||
-RN2.2 |
Trim valve |
|||
-RN3.1 |
Trim valve |
|||
-RN3.2 |
Trim valve |
|||
-RN4.1 |
Trim valve |
|||
-RN4.2 |
Trim valve |
|||
-RN5.1 |
Trim valve |
|||
-RN5.2 |
Trim valve |
|||
-QM1 |
Drain valve, heating medium |
|||
-QM30 |
Shut-off valve, hot water |
|||
-QN17 |
Pressure reduction valve |
|||
-QN44 |
Shut off valve |
|||
-WM3 |
Tundish, cold water |
Included in F1245/F1255 |
||
-WM4 |
Tundish, T&P valve |
Included in F1245/F1255 |
Designations according to standard EN 81346-2.
Marko was here